LANTEK-GAI
Secondary Door Interface
{Site Directory} {Hardware Directory} {LIU-X} {SRB} {Specifications}



Photograph of Secondary Door Interface

 Features
  • Complete remote monitoring of 1 Wiegand or ABA card reader
  • Used with PDI for entry and exit readers per door
  • Up to 500ft from LIU-X / SRB
  • Online Diagnostics
  • Keypad Interface

 

 

Specifications

Card Readers supported
Input Standard
LEDs per card reader
Beeper per card reader
1
Wiegand or ABA (Clock and Data)
2
1
Keypads supported
Configuration
PIN Digits
LEDs per keypad
1
3x4 or 4x4
Configurable
1
Digital Inputs 3 (tamper, access, request to exit)
Terminations
Terminal Spacing
Largest Wire Size
Compression
0.225"
14AWG
Host Communication
Protocol
Baud Rate
Error Detection
RS-485, 2 wire
Lantek 9 Bit
19.2K Baud
CRC-CCITT
Power Required
Temperature Range
Dimensions
12 to 14 VDC, 50 to 300mA.  80% efficient
-5 to 65 degrees C, Operating
3" by 3"

{Site Directory} {Hardware Directory} {LIU-X} {SRB} {Top of Page}


LANTEK-GAI
2131 University Avenue, Berkeley, CA  94704
Tel: (510) 549-0454    FAX: (510) 549-1381
email: sales@lantek-gai.com