LANTEK-GAI
Primary Door Interface
{Site Directory} {Hardware Directory} {LIU-X} {SRB} {Specifications}



Photograph of the Primary Door Interface

  Features
  • Complete remote monitoring and control of 1 door, 1 Wiegand or ABA card reader
  • 4 Fully Supervised Lines
  • REX, Key Switch Inputs
  • Up to 500ft from LIU-X / SRB
  • Online Diagnostics
  • Keypad Interface

 

 

Specifications

Number of Supervised Lines
Type of Line Supervision
Typical Supervision Currents
4
Multilevel
100uA
Card Readers supported
Input Standard
LEDs per card reader
Beeper per card reader
1
Wiegand or ABA (Clock and Data)
2
1
Keypads supported
Configuration
PIN Digits
LEDs per keypad
1
3x4 or 4x4
Configurable
1
Digital Inputs
Isolated Outputs
Configuration
Current @ 24 VDC, 45 degrees C
Fuse
3 (tamper, access, request to exit)
2 Industrial output modules
DC N.O or low current dry contact N.O.
3 Amps continuous, 5 Amps 1 second surge
Per output, 5 Amps
Terminations
Terminal Spacing
Largest Wire Size
Compression
0.225"
14AWG
Host Communication
Protocol
Baud Rate
Error Detection
RS-485, 2 wire
Lantek 9 Bit
19.2K Baud
CRC-CCITT
Power Required
Temperature Range
Dimensions
12 to 14 VDC, 100 to 400mA.  80% efficient
-5 to 65 degrees C, Operating
3" by 6"